B2/AS1 Durability

How long a building element has to keep meeting the Building Code: Table C.1.1.1's 50, 15 and 5 years for the elements it names, Figure 2.1.1.2's steps for those it does not, and Part 3's standards for concrete, steel, timber and the rest. What an element may be made of for that period is E2/AS1's Table C.1.1.1A.

  • B2/AS1Third Edition28 Jul 2025
  • E2/AS1Fourth Edition28 Jul 2025
  • Building Product SpecificationsFirst Edition Amendment 12 Apr 2026
  • F4/AS1Third Edition Amendment 21 Jan 2017

Durability, Table C.1.1.1

The period each nominated building element has to last, not less than, by what it is and where it is. Look an element up here first; Figure 2.1.1.2, on the Assessment face, is for one the table does not name.

Period
Table C.1.1.1 of B2/AS1, one row per situation or function
Situation or function50 yearsor more15 yearsor more5 yearsor more
Acoustic elements
Covered by or integral with structural elements or bracing panels
Behind non-structural claddings or linings
Surface mounted
Balustrade
AllRefer to safety barrier
Battens (Cavity battens for wall cladding systems)
Where wall cladding durability requirement is 15 yearsBattens
Where wall cladding provides bracingBattens
Bracing elements
All situationsAll including the bracing element and fixings
Building wraps (see also wind barriers)
Access requires removal of roof tiles or structural elementsRoof underlay
Where roof cladding durability requirement is 15 yearsRoof underlay
Where wall cladding durability requirement is not less than 50 years (for example, those providing bracing, or where the cladding is very durable such as brick veneer)Wall underlay
Where wall cladding durability requirement is 15 yearsWall underlay
Providing bracing (rigid wind barriers)Wind barriers
Not providing bracing (non-rigid wind barriers)Wind barriers
Cladding (including jointing systems)
StructuralRoofE2/AS1 Table C.1.1.1A
Non-structuralRoofE2/AS1 Table C.1.1.1A
Structural including bracing elementsWallE2/AS1 Table C.1.1.1A
Non-structuralWallE2/AS1 Table C.1.1.1A
Curtain walling
All situationsFrames and fixings
All situationsGaskets, glazing or panelling, and beads
All situationsInternal hardware
Damp-proof course (DPC)
Under structural framingDPCs under timber members
Under non-structural framingDPCs under timber members
Damp-proof membranes (DPM)
DPMs under concrete floor slabsDamp-proofing generally
DPMs applied to the top of concrete slabsDamp-proofing generally
DPMs behind retaining walls used for landscapingDamp-proofing generally
DPMs designed for ready access and replacementDamp-proofing generally
DPM behind tilesDamp-proofing generallySame durability as the tile covering it.1
Tanking, except those designed for ready accessWater-proofing of basements
Tanking designed for ready accessWater-proofing of basements
Decking (timber)
Structural (such as bracing diaphragm)Decking
Non-structural strip deckingDecking
All situationsSub-floor structure
Demountable partitions
All partitions including frame, fixings, and liningPartitions
Doors (including frame)
InternalNon-fire rated doors
ExternalNon-fire rated doors
Furniture and hardwareNon-fire rated doors
InternalFire rated doors
ExternalFire rated doors
Furniture and hardwareFire rated doors
Electrical work
Buried in or under concrete slabs or behind structural linings without ductsWiring
Concealed behind linings or in complex ducts or conduit, or surface mounted in conduitWiring
Wires in easy to access ductsWiring
Concealed and moderately difficult to access or replaceFittings
Surface mountedFittings
Difficult to access or replaceDucting or conduit
Moderately difficult to access or replaceDucting or conduit
Fire rated walls
Structural walls including bracing elements
All others
Fixings
Used to fix structural or difficult to replace building elementsNails and screwsE2/AS1 Table C.1.1.1A
Under water-proof membranesNails and screwsE2/AS1 Table C.1.1.1A
Under roofing membranesNails and screwsE2/AS1 Table C.1.1.1A
Used to fix non-structural or moderately difficult to replace building elementsNails and screwsE2/AS1 Table C.1.1.1A
Used to fix building elements that are difficult to access or replace or that are structural (including structural elements of decks and barriers)Bolts
Used to fix non-structural or moderately difficult to replace building elementsBolts
All situationsBrick ties and fixings
Used to fix structural or difficult to replace building elementsProprietary fixings
Used to fix non-structural or moderately difficult to replace building elementsProprietary fixings
Used to fix structural or difficult to replace building elementsAdhesives
Used to fix non-structural or moderately difficult to replace building elementsAdhesives
Used to fix accessories, door furniture and hardwareFace fixings
Flashings
All flashings to roof cladding, flues and other roof penetrationsRoof, wall, or windowE2/AS1 Table C.1.1.1A
Requires the removal of cladding above the roof to be replacedRoof, wall, or windowE2/AS1 Table C.1.1.1A
Hidden flashings such as behind brick veneer, stucco, or spandrel panelsRoof, wall, or windowE2/AS1 Table C.1.1.1A
Visible and does not require the removal of the cladding to be replacedRoof, wall, or windowE2/AS1 Table C.1.1.1A
Requires the removal of the cladding to be replacedRoof, wall, or windowE2/AS1 Table C.1.1.1A
Flooring sheet or strip
Floor bracing diaphragm
Flooring laid under bottom plates
Flooring laid between bottom plates
Floor coverings
Protective or acoustic coverings
Flue systems
Those built into the floor, wall, ceiling, or roofAll flue systems
Those exposed to view or penetrating the floor, wall, ceiling, or roof through a sleeveAll flue systems
Framing
AllRefer to wall framing or roof framing
Guttering and downpipes
Gutters or downpipes incorporated within the structure (such as downpipes cast into a column or boxed in behind claddings), or secrete gutters (such as hidden verge or valley gutters)
Internal or valley gutters, fascia gutters or built-in downpipes
External gutters or downpipes
Heating appliances
FreestandingSolid fuel
InbuiltSolid fuel
FreestandingGas
InbuiltGas
Permanently wiredElectric
Insulation
All situationsSub-floor
All situationsWalls
Skillion roofCeiling or roof
Accessible ceiling or roof spaceCeiling or roof
Interior wall linings
Structural linings (for example, bracing elements)
Shower linings (excluding behind tiled showers)
Linings behind tiled showersSame durability as the tile covering it.1
Easy to access and replace
Lintels
All situationsSteel angle (brick veneer)
All situationsFlat steel
Plumbing and piping
Cast into concretePiping and fittings
Under slabsPiping and fittings
Installed in a masonry cavity and not ducted or provided with maintenance accessPiping and fittings
Concealed behind wall linings or installed in maintenance ductingPiping and fittings
Surface mounted and easy to replacePiping and fittings
Concealed or moderately difficult to replaceValves
Surface mounted and easy to replaceValves
All situationsFixtures
All situationsOutlets
Protective coatings
Paint systems that are difficult to access or replace
Roofing membranes
Paint systems that are easy to access and replace
Roof framing
All Including trusses, purlins, tile battens, and bracing members
Roofing tile battens
All situations
Safety barriers (balustrade, baluster, and handrail)
All situationsSupport posts, handrails
All situationsBalusters
Septic tanks
Built into or under the structure of a building
Easy to access units (such as in-ground but accessible units)
Effluent field
Stairs and ladders
All situationsStringers
Difficult to replaceTreads
Moderately difficult to replaceTreads
All situationsLadders and rungs
Tiling
Tiling in wet areas including showersWalls and floors
Decorative finish onlyWalls and floorsNo durability requirement under the Building Code.2
Under-floor heating
Buried in concrete slabsHeating coils
Accessible coilsHeating coils
Buried in concrete slabsCables and fittings
Accessible cables and fittingsCables and fittings
Vapour barriers
Behind structural elements or difficult to access and replace
Behind non-structural internal linings
High gloss paint finish
Ventilation
All situationsPlant
Built-in ductingDucting
Easy to access and replaceDucting
All situationsFittings
Vermin proofing
Built into structure
Moderately difficult to access or replace
To drained ventilated cavitySame durability as the cladding covering it.3
Water heaters
Moderately difficult to access or replace (for example, installed in a cupboard)Continuous flow heaters
Easy to access or replace (such as on internal or external wall)Continuous flow heaters
Moderately difficult to access or replace (for example, installed in a cupboard)Storage water heaters
Easy to access but moderately difficult to replaceStorage water heaters
Wall framing including dwangs or nogging
Load-bearing framingTimber or steel
Easy to access lined, non-load-bearing partitionsTimber or steel
Easy to access unlined, non-structural partitions or non-load-bearing demountable partitionsTimber or steel
All situationsStructural steel
Windows
Structural unitsFrame and interior reveals
External window/door joineryFrame and interior reveals
Internal window joineryFrame and interior reveals
Moderately difficult to access or replaceGaskets, glazing, and glazing beads
Hardware
  • the element in this situation lasts not less than this long
  • a note in place of a period: the element takes another's, or has none
  • in mono under a row: E2/AS1 Table C.1.1.1A gives the zones its material lasts this long in
  • ≠ and a number: the documents say different things here. They are set out under the table, in the same order on every durability table
  1. Same durability as the tile covering it.
  2. No durability requirement under the Building Code.
  3. Same durability as the cladding covering it.

Where the documents differ

  1. Hidden is not always 50 yearsE2/AS1 · B2/AS1

    E2/AS1 Table C.1.1.1A's note (3) says hidden elements require 50 years under the Building Code, and exposed and sheltered ones 15; the table itself heads one column 15 years and one 50 years for hidden elements, and prints both against every hidden row: hot-dip galvanised nails hidden are acceptable in zones B, C and D for 15 years and B and C for 50. B2/AS1 Table C.1.1.1 does not divide by what shows. It gives 15 years to wall underlay where wall cladding durability requirement is 15 years, to cavity battens where wall cladding durability requirement is 15 years, and to nails and screws used to fix non-structural or moderately difficult to replace building elements, which takes in nails punched and puttied under paint, the fixings E2's note (6) counts as hidden. Under both, B2.3.2 asks a hidden element to last at least as long as the element hiding it.

    E2/AS1 Table C.1.1.1A note (3), E2/AS1 Table C.1.1.1A note (6), B2/AS1 Table C.1.1.1, NZBC B2.3.2

  2. A flashing's period: what replacing it takes, or what showsB2/AS1 · E2/AS1

    B2/AS1 decides a flashing by what replacing it takes: 50 years where the cladding, or the cladding above a roof, has to come off to replace it, whether or not the flashing shows; 15 years where it is visible and does not. E2/AS1 decides by what shows: note (3) reads exposed and sheltered elements at 15 years, and the COMMENT to 4.2.1.1 gives 15 years to flashings exposed, partially exposed or accessible. A head flashing that shows below the cladding it is lapped under is 50 years by the first reading and 15 by the second.

    B2/AS1 Table C.1.1.1, E2/AS1 Table C.1.1.1A note (3), E2/AS1 4.2.1.1 COMMENT

  3. No column for an element that shows and needs the longer periodB2/AS1 · E2/AS1

    B2/AS1 gives 50 years to elements that are not hidden: a roof or wall cladding that is structural or provides bracing, and a flashing replaced only by removing cladding. E2/AS1 Table C.1.1.1A heads its 50-year column for hidden elements only, so its exposed and sheltered columns go no further than 15 years. E2/AS1 answers the longer period in its own text for one cladding alone: plywood used as bracing, at 9.8.9.2.

    B2/AS1 Table C.1.1.1, E2/AS1 Table C.1.1.1A, E2/AS1 9.8.9.2

Per B2/AS1 Table C.1.1.1: Durability requirements of nominated building elements, pp.15–21; B2/AS1 2.1.1.1, Figure 2.1.1.2, 3.3.1.1 and 3.3.2.1: values stated in the paragraphs listed.