G4/AS1 Ventilation

A household unit room by room: what each room needs to be ventilated, the extract its fixtures call for, and the trickle ventilators the unit needs, read from G4/AS1 Part 2.

  • G4/AS1Fifth Edition28 Jul 2025

The unit

The unit's type sets how many people it is taken to hold, which is what sizes its trickle ventilators. Whether it has only one external wall changes most of what follows.

Household unit type

The unit

Occupants
3
Table 2.2.2.5A

Rooms

Add each room. What it needs depends on what it is, whether it has an external wall, and what is in it.

Remove “Living or dining 1”?

Everything answered about this room goes with it.

Openable
1m²
2.2.1.2
Extract
–
2.2.1.5
  1. Net openable area

    At least 1 m², 5% of 20 m².

    2.2.1.2

Remove “Kitchen 1”?

Everything answered about this room goes with it.

Openable
0.6m²
2.2.1.2
Extract
50L/s
2.2.1.5
  1. Net openable area

    At least 0.6 m², 5% of 12 m².

    2.2.1.2

  2. Extract flowrate

    No mechanical extract is required of this Kitchen by G4/AS1: it has an external wall, so 2.1.1.3 does not send it to Section 2.3, and 2.2.1.5 names only cooktops, showers and baths.

    2.1.1.3, 2.2.1.5

Remove “Bathroom 1”?

Everything answered about this room goes with it.

Openable
0.25m²
2.2.1.2
Extract
25L/s
2.2.1.5
  1. Net openable area

    At least 0.25 m², 5% of 5 m².

    2.2.1.2

  2. Extract flowrate

    No mechanical extract is required of this Bathroom by G4/AS1: it has an external wall, so 2.1.1.3 does not send it to Section 2.3, and 2.2.1.5 names only cooktops, showers and baths.

    2.1.1.3, 2.2.1.5

Remove “Bedroom 1”?

Everything answered about this room goes with it.

Openable
0.6m²
2.2.1.2
Extract
–
2.2.1.5
  1. Net openable area

    At least 0.6 m², 5% of 12 m².

    2.2.1.2

Remove “Bedroom 2”?

Everything answered about this room goes with it.

Openable
0.6m²
2.2.1.2
Extract
–
2.2.1.5
  1. Net openable area

    At least 0.6 m², 5% of 12 m².

    2.2.1.2

Gas-fuel appliances

Part 3 is a space with gas appliances in it: the permanent vents a non room-sealed appliance needs on top of whatever Part 2 already asks of the space, or the space's mechanical ventilation.

Gas appliance flues

Where on the dwelling a gas appliance's flue may end, whether the appliance is room-sealed or not: a water heater on an outside wall as much as a fire.

This tool reads G4/AS1 Fifth Edition, effective 28 July 2025, and reports what Part 2 says about ventilating spaces within buildings. It does not cover Part 3 flues and appliances, car parks, or the outdoor air flow rates that Section 2.3 hands to NZS 4303 and AS 1668.2. It is not a substitute for reading the document, for the judgement of a suitably qualified person, or for the decision of the building consent authority. Table 2.2.2.5B: Total required equivalent aerodynamic area for the space (mm2), p.10 (Paragraph 2.2.2.5 g))