Fully vented
Section 8Every trap has its own vent, joined into branch vents and up to the stack vent, with a relief vent beside a taller stack. Any fixture, any layout, any height.
Its four ways of venting a building's sanitary plumbing, what each asks for and the sizes to design to, and which edition a consent is read against.
They differ in one thing: how air reaches the pipes, so that water leaving one fixture does not pull the water out of another's trap. The more venting a system has, the further a fixture can be from its stack; the less it has, the closer and fewer the fixtures have to be.
Every trap has its own vent, joined into branch vents and up to the stack vent, with a relief vent beside a taller stack. Any fixture, any layout, any height.
Fixtures grouped on one branch share a group vent instead of a vent each; every branch into the stack is still vented. Bathrooms and toilet rooms, with far fewer vents.
No trap or branch vents: each fixture runs its own short pipe to a stack of at least DN 100, whose own vent is the only air. Wet rooms stacked over each other, close to the stack.
Fixtures connect as in the single stack; a relief vent beside the stack, tied in by cross-vents, lets the same DN 100 stack take more load or more floors.
G13's third acceptable solution, G13/AS3, is this standard: the 2021 edition with Amendment 1, changed at 2.2, 3.19, 4.4, 4.6.6 and Section 14. The 2025 edition has replaced 2021 at Standards New Zealand but no amendment to G13 cites it yet, so a design to 2025 is an alternative solution, read as the edition stands, without G13's five changes.
G13 Amendment 10, its references and G13/AS3 1.0The definition of a fully vented system includes a relief vent, but the clause that sets when one is needed asks for it only where at least 1 floor lies between the stack's highest and lowest branches. A two-storey house with its bathrooms on adjacent floors does not need one.
AS/NZS 3500.2:2025 8.2.2 (b), 8.5.3.1The clause on single stack sizes points to the commercial table of the modified system, not the single stack's own. Read literally, a single stack in an office would take the modified system's loads without its relief vent.
AS/NZS 3500.2:2025 9.7.1, Tables 9.7.1(B) and 9.7.2(B)