C/AS1 Protection from Fire

Based on C/AS1 Second Edition Amendment 1 (effective 28 July 2025; the previous edition cannot be used from 1 August 2026). First check whether your design is within scope, then work through each Part to see what this building needs, with paragraph references on every line.

  • C/AS1Second Edition Amendment 128 Jul 2025
  • C/AS2Second Edition28 Jul 2025
  • Building Product SpecificationsFirst Edition Amendment 12 Apr 2026
  • NZS 4514:2021
  • Building Regulations 1992

Part 1, Table 1.1.1.1

Scope

C/AS1 covers risk group SH only. This step confirms your design has not been pushed into C/AS2 or C/VM2.

No classified use set in the project. Set it once and this page knows whether the building is risk group SH, which is all C/AS1 covers.

Building type

Other uses

C/AS2 exclusions

C/AS1 applies (risk group SH)

Under Table 1.1.1.1 this building is within risk group SH, so C/AS1 can be used to demonstrate compliance with C1–C6. The Parts below are now unlocked.

  • Only an all-out evacuation strategy is provided for (1.1.2.2)
  • Hazardous substances are not covered (1.1.2.3)
  • If any requirement cannot be met, the acceptable solution cannot be used at all; use C/VM2 or an alternative solution instead (1.1.3.3)

Part 2, Appendix C

Fire safety system

The sprinkler option chosen here affects every Part that follows.

Sprinkler system

All three extend travel distances and remove the external wall FRR. Only NZS 4515 / 4541 unlock the exemptions for roofs, cladding, external safe paths and the fire appliance hard-standing.

  1. Sprinklers

    Not selected

    C/AS1 never mandates sprinklers. Installing them raises DEOP/TOP to 40/100 m and removes the external wall FRR; NZS 4515/4541 also remove the roof, cladding, external safe path and hard-standing distance requirements.

    3.3.1.1, 5.1.1.1

  2. Firecell floor area

    No limit

    2.1.1.1

Part 3

Means of escape

Measure the path from the most remote room to the exit against Table 3.3.1.1, then check whether there is only one direction of travel once outside the building.

Measured distances

Start within 1.0 m of the most remote point; measure orthogonally 1.0 m from walls if furniture positions are unknown; stairs count as plan length plus landings; ladders count as vertical height (3.3.2.1).

Once outside the building

Room occupant load

  1. Dead end open path

    12000 mm (12 m) ≤ 35000 mm (35 m)

    Column used: Household unit + Type 1. A single escape route is permitted (3.1.2.1).

    Table 3.3.1.1

  2. Total open path

    18000 mm (18 m) ≤ 75000 mm (75 m)

    Table 3.3.1.1

  3. External safe path

    Not required

    There is more than one direction of escape once outside, so no external safe path is needed.

    3.3.5.1

Part 4

Internal separations and surface finishes

Fire separations between units, and the limits on foamed plastics and combustible insulation.

Ancillary spaces

Wall or ceiling systems

  1. Within the unit

    Not required

    A single household unit is one firecell; its internal floors and partitions need no FRR.

    Appendix B

  2. Interior surface finishes

    No requirement

    Without foamed plastics or combustible insulation there are no surface finish requirements in SH.

    4.2.1.1

Part 5

External walls and the boundary

Fire resistance required of external walls, eaves and cladding.

Household unit1000 mm (1 m)Floor inside one unit: no FRRCladding finished facedimension from hereRelevant boundaryOther property800 mm350 mmFRR 30/30/30

What is on the other side

If the other property is a road, railway or public open space, the relevant boundary is the far side of it (Appendix B).

Eaves

Other situations

  1. External wall

    FRR 30/30/30 required, both directions

    Less than 1 m from the relevant boundary. The wall must resist fire from both directions; any unrated window or door is an unprotected area (Appendix B), so openings within 1 m must be rated or removed.

    5.1.1.2(a)

  2. Eaves

    FRR 30/30/30 required

    Where the external wall needs an FRR, the eaves projection must be 30/30/30 or the wall extended to the roof underside.

    5.2.1.1

  3. Cladding materials

    Non-combustible, limited combustible or Type A

    Less than 1 m from the relevant boundary, regardless of height.

    Table 5.3.1.1, BPS 8.4.1

Part 6

Fire appliance access

Only triggered for multi-unit buildings with more than 2 units that are remote from the street boundary.

Site conditions

  1. Fire appliance access

    N/A

    Part 6 applies to multi-unit buildings only.

    6.1.1.1

Part 7

Fireplaces and heating appliances

Masonry chimney and hearth dimensions for open fires are written directly into C/AS1; solid fuel, gas and oil appliances each reference a different standard.

Appliances

  1. Heating appliances

    Not selected

    Without a fireplace or combustion appliance, Part 7 reduces to 7.2: electrical installations to G9.

    7.2.1.1

This tool is an educational summary of C/AS1. Paragraph numbers refer to the official documents on building.govt.nz. Design and consent submissions must rely on the source text.