D1/AS1 Access Routes
Stairways, winders and spiral stairs, ramps, fixed ladders, doors, routes, walking surfaces and stair lighting under D1/AS1, worked from your numbers, and where NZS 4121 asks for something different.
- D1/AS1Second Edition Amendment 61 Jan 2017
- F4/AS1Third Edition Amendment 21 Jan 2017
- C/AS1Second Edition Amendment 128 Jul 2025
- C/AS2Second Edition28 Jul 2025
- G8/AS1First Edition Amendment 214 Feb 2014
- NZS 4121:2001
- Building Regulations 1992
Stair design
From the storey height, the fewest risers Table 6 allows and the riser that gives, the tread that goes with it, and the landings Table 7 asks for. Add risers to make it shallower.
Stairway type
The design
- Risers
- 15
- Table 6
- Riser
- 183.7mm
- Table 6
- Tread, at least
- 280mm
- Table 6
- Pitch at that tread
- 33.27°
- Table 6
- Intermediate landings
- 0
- Table 7
- 115 risers of 183.7 mm, treads 280 mm deep
- 2One flight of 15 risers, no landing needed
- 3A handrail on at least one side, between 900 mm and 1 m above the pitch line
Risers
15 risers, the fewest Table 6 allows for 2755 mm (2.755 m) on a Main private stairway. Add one to make it shallower.
4.1.1, Table 6
Riser height
183.7 mm each, over 15 risers, against a maximum of 190 mm.
4.1.1, Table 6
Tread depth
No less than 280 mm, nosing included. With the nosing taken off, the going is 280 mm, and the pitch line slope is 33.27°, against a maximum of 37°.
4.1.1, Table 6, Figure 12, Definitions p.15
Nosing
No nosing: the going is the full 280 mm tread depth.
4.1.2, Figure 12, 4.1.6 b)
Landings
None between floors: 2755 mm (2.755 m) is within the 4000 mm (4 m) Table 7 allows between landings for Main private stairways. Landings at top and bottom still.
4.3.1, 4.3.2, Table 7
Landing size
No less than 900 mm long, and no narrower than the stair it serves (1000 mm (1 m)).
4.3.3, 4.3.4
Sides needing a handrail
At least one side: 1000 mm (1 m) wide, up to the 2000 mm (2 m) that 6.0.1 sets, with 15 risers.
6.0.1
D1 only sets the handrail. What fills the side below it is F4/AS1's. Where someone could fall 1 m or more, the side needs a barrier. In housing, or anywhere children under 6 are likely, no gap in it may let a 100 mm sphere through, and the triangle between the tread, riser and bottom rail must not let a 150 mm sphere through. Elsewhere, gaps may be up to 300 mm between balusters or 460 mm between rails. F4/AS1 Figures 1–4 show barriers a small child can't easily climb. NZBC F4.3.1, F4/AS1 1.2.1, 1.2.2, Figures 1–4
Triangle under the bottom rail
With a 183.7 mm riser and a 280 mm going, a bottom rail 100 mm above the pitch line, where F4/AS1 Figure 4 draws it, leaves a triangle a 213 mm sphere passes through, where F4/AS1 1.2.1 c) allows under 150 mm. The sphere is the limit that governs, not the figure's 100 mm.
F4/AS1 1.2.1 c), F4/AS1 Figure 4
How close the rail has to sit
On this stair the bottom rail has to sit no more than 24 mm above the pitch line, square to it, to keep the triangle under 150 mm, against the 100 mm F4/AS1 Figure 4 draws.
F4/AS1 1.2.1 c), F4/AS1 Figure 4
Figure 4's pitch
This stair's pitch is 33.3°, not steeper than the 35° F4/AS1 Figure 4 is drawn at. Read as the figure's condition, its raking rails are not the construction for this stair. The reading is ours, and the COMMENT under F4/AS1 1.2.1 says near-horizontal rails are easily climbed.
F4/AS1 Figure 4, F4/AS1 1.2.1 COMMENT 3
Ramp design
From the rise, the steepest slope Table 3 allows for the type, the run that gives, and the landings Table 5 asks for. Flatten the slope to lengthen the ramp.
Type of ramp
The design
- Slope, 1 in
- 12
- Table 3
- Run
- 6000mm
- 3.1.1
- Intermediate landings
- 0
- Table 5
- 11 in 12: 6000 mm (6 m) of ramp for 500 mm of rise
- 2Handrails both sides, between 900 mm and 1 m above the pitch line
- 3300 mm level extension at each end
- 475 mm upstand along an open side
Slope
1 in 12, the steepest Table 3 allows for Accessible ramps.
3.1.1, Table 3
Run
6000 mm (6 m) of horizontal run for 500 mm of rise at 1 in 12, before landings.
3.1.1
Landings
None between the ends: 500 mm is within the 750 mm Table 5 allows between landings. Landings at top and bottom still.
3.3.1, Table 5
Sides needing a handrail
Both sides: an accessible ramp steeper than 1 in 20 takes handrails on both sides.
6.0.3
D1 only sets the handrail. What fills the side below it is F4/AS1's. Where someone could fall 1 m or more, the side needs a barrier. In housing, or anywhere children under 6 are likely, no gap in it may let a 100 mm sphere through. Elsewhere, gaps may be up to 300 mm between balusters or 460 mm between rails. F4/AS1 Figures 1–4 show barriers a small child can't easily climb. NZBC F4.3.1, F4/AS1 1.2.1, 1.2.2, Figures 1–4
Also under NZS 4121
NZS 4121:2001 is an acceptable solution too, because the Building Act says so at s119, and it sets an accessible ramp of its own. These are the places it asks for something D1/AS1 does not, worked on the ramp above. The D1 and NZS 4121 tab has the whole comparison.
Handrail height
D1/AS1 asks for 900–1000 mm (0.9–1 m) above the pitch line and NZS 4121 asks for 840–900 mm. 900 mm is the only height that meets both, so draw it. Difference 1 on the comparison tab.
6.0.3, 6.0.6, NZS 4121 6.4.2.6
Where the landings fall
D1/AS1 counts rise, a landing every 750 mm up; NZS 4121 counts run, a landing every 9000 mm (9 m) along. At 1 in 12 this ramp runs 6000 mm (6 m), which is short of both: neither asks for a landing part way up. Difference 3 on the comparison tab.
Table 5, NZS 4121 6.5.1, NZS 4121 6.5.2
Open side of the ramp
Where a ramp has a drop at its side D1/AS1 asks for a 75 mm upstand. NZS 4121 takes an upstand of 75 mm or an edge rail no higher, and asks for a rail at mid-height between that and the handrail, so a wheel or a stick cannot go over the edge. Difference 6 on the comparison tab.
3.1.3, NZS 4121 6.4.2.5
Everything else
The steepest slope and the clear width: the same 2 figures in both documents, so a ramp that meets D1/AS1 meets them.
Table 3, NZS 4121 6.4.2.2, 3.2, NZS 4121 6.4.2.4
Winders and tapered treads
A stairway that turns on its treads, and the going on the pitch line D1/AS1 names for it. The treads radiate from one centre, as a uniform taper angle means, and the going is measured straight from nosing to nosing where the line crosses them.
What turns
Stairway type
The turn
- Pitch line from centre
- 450mm
- Figure 18
- Going on the line
- 232.9mm
- 4.5.1
- Treads in the turn, at most
- 2
- Table 6
Stairway type
Winders on a Main private stairway, which 4.5.1 accepts.
4.5.1
Pitch line
At the middle of the stairway, which is narrower than 1000 mm (1 m): 450 mm from the centre.
4.5.2, Figure 18
Riser
180 mm, against a maximum of 190 mm for Main private stairways.
4.5.1 a), 4.5.1 b), Table 6
Tread on the pitch line
On the pitch line, the going is 232.9 mm, and with the 0 mm nosing the tread is 232.9 mm, short of the 280 mm minimum for Main private stairways.
4.5.1 a), Table 6, Figure 11
Pitch on the pitch line
On the pitch line, 37.7° is steeper than the 37° maximum for Main private stairways.
4.5.1 a), Table 6, Figure 11
Against the straight flights
On the pitch line, the going is 232.9 mm, less than the straight flights' 280 mm.
4.5.1 c), Figure 18
How far the winders turn
90°, no more than 180°.
4.5.1 e)
Treads in the turn
Every line needs a going of at least 280 mm, which allows no more than 2 treads in this 90° turn, and 3 are drawn.
4.5.1 a), 4.5.1 c), Table 6
Another route
At this width, BS 585 Part 1 is also an acceptable solution for the winders: it covers stairways 770 to 1200 mm (1.2 m) wide.
4.5.3
One fixed ladder
A ladder's figures against those 5.2 to 5.4 set for its kind, and whether it needs safety hoops.
Kind
What this ladder needs
- Between landings, at most
- 6000mm
- 5.2.1 d)
- Safety hoops
- Not needed
- 5.1.2
Slope
65°, within 60° to 70°.
5.2.1 a)
Tread or rung
120 mm wide, at least 100 mm.
5.2.1 b)
Spacing
225 mm centres, within 200 to 250 mm.
5.2.1 b)
Width
500 mm between the stiles, at least 450 mm.
5.2.1 c)
Clearance behind
100 mm between the treads and any solid object behind, at least 50 mm.
5.2.1 e) ii)
Handrails and openings
Handrails on both sides, 550 to 750 mm apart, no more than 450 mm above the stile, starting no lower than 900 mm and running 900 mm above the upper landing, with 50 mm for the hand along them; openings at landings of at least 1150 mm (1.15 m).
5.2.1 e) i), 5.2.1 f), 5.2.1 g)
Height between landings
2700 mm (2.7 m), no more than 6000 mm (6 m).
5.2.1 d)
Safety hoops
Not needed: the ladder rises no more than 6 m, in one section, and not from a landing or platform.
5.1.2
Spacing
The same spacing throughout, within ±5 mm.
5.1.6
The door
A door can be on an accessible route and an escape route at the same time. D1/AS1 sets the accessible minimum and C/AS1 or C/AS2 the escape one, by risk group, and a door that is both has to meet whichever is larger.
Which routes is this door on?
- 1760 mm clear opening, at least 760 mm
- 2300 mm of wall beside the handle
- 3Handle between 900 and 1200 mm (1.2 m) up
Clear opening
760 mm, against a minimum of 760 mm, which is D1/AS1's accessible door width.
7.0.3
Also under NZS 4121
NZS 4121:2001 is an acceptable solution too, because the Building Act says so at s119, and it sets doors on an accessible route. These are the places it asks for something D1/AS1 does not. The D1 and NZS 4121 tab has the whole comparison.
Force to open
NZS 4121 caps how hard a door may be to open: 38 N on a hinged door outside, 22 N on one inside, 22 N on a sliding door, fire doors excepted. D1/AS1 sets no force at all, so a self-closer specified to D1/AS1 alone can fail this.
NZS 4121 7.3.5
Vision panel
D1/AS1 asks for one only where a door swings both ways. NZS 4121 sizes the panel for doors on an accessible route, which can be read as every door on the route. Neither document settles it, so say which reading the drawings took. Difference 10 on the comparison tab.
7.0.4, Figure 28, NZS 4121 7.3.2 (c), NZS 4121 Figure 21
Everything else
The clear opening, the handle height and the wall beside the handle: the same 3 figures in both documents, so a door that meets D1/AS1 meets them.
7.0.3, NZS 4121 7.3.1, 7.0.5, NZS 4121 7.3.7 (a), 7.0.1, NZS 4121 7.3.3
The access route
Height clearance depends on what the route is for, and how far a thing may stick into it depends on how high off the floor it is.
- 12100 mm (2.1 m) headroom required
- 2Beam or ceiling at 2400 mm (2.4 m), clears the 2100 mm (2.1 m)
- 3What may stick out of the wall: less than 100 mm below 800, 60 mm from 800 to 1600, 200 mm above
Height clearance
2400 mm (2.4 m), against a minimum of 2100 mm (2.1 m) for Pedestrian access routes (unlimited length).
1.4.1, Table 1, Figure 3
Seats and rooms
How many wheelchair spaces a room of seats needs, and how many guest rooms are accessible, by D1/AS1 with NZS 4121's count beside it.
A room of seats
Guest accommodation
What this building needs
- Wheelchair spaces
- 2
- 8.1.1
- Accessible units
- 2
- Table 9
Wheelchair spaces
300 seats need 2 wheelchair spaces; 2 provided.
8.1.1
Under NZS 4121
NZS 4121, counting 300 people and part of a band, asks for 3, more than the 2 provided.
NZS 4121 12.2.1.1 (a), NZS 4121 12.2.1.1 (b)
Accessible units
40 guest units need 2 accessible units; 2 provided.
9.1.1, Table 9
Under NZS 4121
NZS 4121 asks for the same 2, and counts cabins, tent sites and caravan sites as units too.
NZS 4121 Table 2
In each unit
A 1500 mm (1.5 m) turning circle in the bedroom, sitting and dining areas, a bathroom to G1/AS1, and an accessible kitchen or tea and coffee facilities in line with the other units.
9.2.1
The walking surface
Table 2 answers wet and dry separately, and level and sloping separately. Which pair applies is set by the slope, in the table's own Notes 1 and 2.
Table 2 at a glance
Pick a cell to check it below.
- Acceptable
- Only if a test shows it
- Not acceptable (blank)
| Surface | Level, dry1 in 50 or flatter | Level, wet1 in 50 or flatter | Sloping, drySteeper than 1 in 50 | Sloping, wetSteeper than 1 in 50 |
|---|---|---|---|---|
| Timber | ||||
| Uncoated smooth | ||||
| Uncoated profiled – across profileNote 4 | ||||
| Uncoated profiled – along profileNote 4 | ||||
| Coated (paint, polyurethane, etc) | ||||
| Coated and sand/grit impregnatedNote 5 | ||||
| Portland cement concrete | ||||
| Smooth trowelled finish (Class U3)Note 6 | ||||
| Broomed (Class 5 or 6) or wood float finish (Class U2)Note 6 | ||||
| Coated (paint, polyurethane, etc) | ||||
| Coated and sand/grit impregnatedNote 5 | ||||
| Exposed aggregate finish – rounded aggregate | ||||
| Exposed aggregate finish – crushed aggregate | ||||
| Asphaltic concrete | ||||
| Marble and granite | ||||
| Polished surfaceNote 7 | ||||
| Honed finishNote 8 | ||||
| Flamed finish | ||||
| Fully sandblasted surfaceNote 8 | ||||
| Patterned sandblasted surfaceNote 9 | ||||
| Split slate | ||||
| Terrazzo | ||||
| Polished | ||||
| Honed | ||||
| Sandstone | ||||
| Ceramic tiles | ||||
| Unglazed – smooth finish | ||||
| Unglazed – profiledNote 9 | ||||
| Unglazed – grit finishNote 10 | ||||
| Glazed – smooth or polished finishNote 7 | ||||
| Glazed – profiledNote 9 | ||||
| Glazed – grit finishNote 10 | ||||
| Clay pavers | ||||
| Wire cut | ||||
| Smooth texture | ||||
| Concrete pavers | ||||
| Dry press concrete | ||||
| Interlocking concrete block pavingNote 11 | ||||
| Moulded surface (e.g. simulated slate or concrete cobbles) | ||||
| Compressed fibre-cement sheet | ||||
| Uncoated | ||||
| Coated (paint, polyurethane, etc) | ||||
| Coated and sand impregnatedNote 5 | ||||
| Rubber tiles/sheeting | ||||
| Smooth | ||||
| ProfiledNote 9 | ||||
| Vinyl and linoleum | ||||
| Smooth or with imprinted pattern | ||||
| Profiled (studs or ribs)Note 9 | ||||
| Grit/flaked finish | ||||
| Carpet | ||||
| Tufted or loop pileNote 13 | ||||
| Artificial turfNote 13 | ||||
| Timber composites (chipboard, cork tiles, etc) | ||||
| Uncoated | ||||
| Coated (paint, polyurethane, etc) | ||||
| Coated and sand/grit impregnatedNote 5 | ||||
| Anti-slip tapesNote 14 | ||||
- Level surfaces including surfaces with slopes no steeper than 1:50.
- Sloping surfaces with slopes greater than 1:50 but less than 1:10 for wet conditions, or less than 1:8 for dry conditions.
- Acceptability as shown is based on stair treads without slip resistant nosings. When testing stair treads without nosings acceptability for slip resistance should be on a slope of 1:10. With slip resistant nosings at least 50 mm wide, acceptability criteria for stair treads is based on the requirements for level surfaces.
- Profile at right angles to direction of pedestrian traffic. Algal growth on uncoated timber walkways significantly reduces slip resistance when wet and requires regular removal, e.g. by high pressure waterblasting.
- The sand/grit, which is sprinkled over the complete surface of the final paint coating, should be a hard angular material such as silica sand or calcined bauxite. The particle size should not be less than 0.2 mm so that it is not submerged by the coating and not greater than about 2 – 3 mm so that it remains tightly bound to the surface. If overpainted, testing is required to establish acceptability of slip resistance.
- Concrete surface finishes complying with NZS 3114.
- Glazed or polished surfaces are unsuitable in either wet or dry conditions for sloping surfaces or for stairs because of the effect of foot placement, even though test measurements may indicate adequacy.
- The coefficient of friction can vary significantly with the extent of surface preparation.
- It is noted in AS 4586 that the pendulum slip resistance tests prescribed in that Standard may not be suitable for heavily profiled (or patterned) surfaces.
- When the grit finish has a “feel” rougher than 80 grit sandpaper, the surface may be deemed to have acceptable wet slip resistance, for either level or sloping surfaces or for stair treads, without testing.
- Interlocking concrete block paving to NZS 3116.
- To meet durability requirements of NZBC B2, the surface should have at least a five year life under normal maintenance.
- Validity of the listed typical values for coefficient of friction is uncertain as the test methods may not be applicable to carpets.
- Anti-slip tapes will normally require regular replacement to remain effective. To ensure foot contact, tapes should be placed at right angles to the line of travel and be spaced at no more than 150 mm centres.
Check one surface
Condition
Where it is
Which columns apply
1 in 20 is steeper than 1 in 50 and flatter than the 1 in 10 that Note 2 sets for wet conditions, so the sloping surface columns apply.
Table 2 Note 2
Acceptable
No. Timber, Uncoated smooth does not have acceptable wet slip resistance as a sloping surface.
Table 2, 2.1.1
Stairway lighting
These two tables are for reference: watts per m² for the lamps of 1998 (D1/AS1 Table 8) and 2014 (G8/AS1 Table 1), neither with LEDs. What a design has to meet is the light level behind them, and that's in the Requirements.
Watts per m² in each table
| Fitting | D1 private, service100 lux at the treads | D1 accessible, common150 lux at the treads | G8 stair and lift lobby20 lux on the floor | G8 corridor20 lux on the floor |
|---|---|---|---|---|
| Incandescent (plastic shade) | 20 | 30 | 10 | 12 |
| Incandescent (general diffusing enclosure) | 25 | 35 | 12 | 15 |
| Flourescent 36/58 W cool white (enclosed diffusing fitting)G8: Fluorescent 36 W cool white (enclosed diffusing fitting) | 7 | 10 | 4 | 7 |
| Flourescent compact single ended 16-38 W (enclosed diffusing fitting)G8: Fluorescent compact single-ended 11-16 W (enclosed diffusing fitting) | 10 | 15 | 5 | 8 |
| Discharge 50/80 W mercury or high pressure sodium (enclosed diffusing fitting)G8: Discharge 50 W high pressure sodium (enclosed diffusing fitting) | 7 | 10 | 5 | 5 |
Rows pair the same kind of fitting; where the two tables name it differently, both names are given. Neither table has LEDs.
What to buy
A lamp's box gives lumens (lm) and watts; D1 and G8 ask for lux, which is lumens per m² reaching the treads or the floor. Not all of a lamp's light gets there, so as a rough first pick allow about 2.5 lm from the lamps for every lux you need, per m² of floor:
150 lux for accessible and common stairways: about 375 lm per m², which is roughly 3.8 W of LED per m².
100 lux for private and service stairways: about 250 lm per m², which is roughly 2.5 W of LED per m².
20 lux for the rest of the route, landings and lobbies: about 50 lm per m², which is roughly 0.5 W of LED per m².
For example, the 7 m × 4 m stair lobby both tables are based on is 28 m². At 150 lux it needs about 10500 lm in total: say 14 LED lamps of 800 lm, about 8 W each.
Our rule of thumb, not the documents': about 50% of the light reaches the floor, 80% of that is left once the lamp ages and gets dusty, and an LED gives about 100 lm per watt. Narrow-beam downlights and dark finishes need more; a lighting designer can work it out properly.
Colour temperature isn't set by D1 or G8. Warm white (about 3000 K) is usual in homes and neutral white (about 4000 K) in common areas; either is fine. What matters more on a stair is seeing the edge of each tread: avoid glare, and on an accessible stair make the nosings contrast with the treads (D1/AS1 4.1.7).
D1/AS1 and NZS 4121
Both are acceptable solutions. D1/AS1 is MBIE's; NZS 4121:2001 is one because the Building Act says so (s119). Most figures match. Where they don't, the row has a ≠ and a number, and the list under the table says what's different. A dash means that document doesn't set it.
| What | D1Clause D1 and D1/AS1 | NZS 41212001 edition |
|---|---|---|
| Routes | ||
| Clear widthD1 2.2.1 · NZS 4.5.3, 7.2.1 | 1200 mm (1.2 m) | 1200 mm (1.2 m); corridors 1200 mm (1.2 m) |
| HeadroomD1 Table 1 · NZS 4.5.2 | 2100 mm (2.1 m); 2000 mm (2 m) where it's under 2 m long | 2100 mm (2.1 m); 2000 mm (2 m) where it's under 2 m long |
| Steepest cross fallD1 1.2.2 · NZS 6.1 (b) | 1 in 50 | 1 in 50 |
| Small change of levelD1 1.3.1, 1.3.2 · NZS 7.1.4, 6.6.2 | A weather stop up to 20 mm. Anything more is a ramp. | Up to 20 mm needs no ramp. More: a 1 in 8 ramp up to 450 mm long. |
| Ramps | ||
| Steepest rampD1 Table 3 · NZS 6.4.2.2, C6.4.2.2 | 1 in 12 | 1 in 12 (1 in 14 recommended) |
| Ramp widthD1 3.2 · NZS 6.4.2.4 | 1200 mm (1.2 m) | 1200 mm (1.2 m) |
| Ramp landingsD1 Table 5 · NZS 6.5.1, 6.5.2 | Every 750 mm of rise, 1200 mm (1.2 m) long | Every 9000 mm (9 m) of run, at least 1200 mm (1.2 m) |
| Ramp handrailsD1 6.0.3, 6.0.6 · NZS 6.4.2.6 | Both sides when steeper than 1 in 20; 900–1000 mm (0.9–1 m) | Both sides; 840–900 mm |
| Open side of a rampD1 3.1.3 · NZS 6.4.2.5 | 75 mm upstand | 75 mm upstand or edge rail, plus a middle rail |
| Kerb rampD1 3.4.1 · NZS 13.4.3.1 | 1 in 8 | 1 in 8, up to 1500 mm (1.5 m) long |
| Accessible stairs | ||
| Riser / treadD1 Table 6 · NZS 8.4.2 (b) | 180 / 310 mm | 180 / 310 mm |
| Most rise in one flightD1 Table 7 · NZS 8.3.2 | 2500 mm (2.5 m) | 2500 mm (2.5 m) |
| Width between handrailsD1 4.2.1 · NZS 8.4.1 | 900 mm | 900 mm |
| Landing lengthD1 4.3.4 · NZS 8.3.6.1 | 900 mm | 1200 mm (1.2 m) |
| Handrail heightD1 6.0.6 · NZS 8.6.4.3 | 900–1000 mm (0.9–1 m) | 900–1000 mm (0.9–1 m) |
| Handrail extensionD1 6.0.4 · NZS 8.6.5.1 | 300 mm at each end | 300 mm at the top; 300 mm plus one going at the bottom |
| Doors | ||
| Clear openingD1 7.0.3 · NZS 7.3.1 | 760 mm | 760 mm |
| Handle heightD1 7.0.5 · NZS 7.3.7 (a) | 900–1200 mm (0.9–1.2 m) | 900–1200 mm (0.9–1.2 m) |
| Wall beside the handleD1 7.0.1 · NZS 7.3.3 | 300 mm | 300 mm |
| Force to openNZS 7.3.5 | 38 N exterior hinged; 22 N interior; 22 N sliding | |
| Vision panelD1 7.0.4, Figure 28 · NZS 7.3.2 (c), Figure 21 | In a door that swings both ways | In a door on an accessible route, to Figure 21 |
| Lifts | ||
| When a lift is neededD1 Clause D1.3.4(c), 12.0.1 · NZS 9.1.3 | 4+ storeys; 3 storeys with 50+ people upstairs; 2 storeys with 40+ | 4+ storeys. Not needed at 2 storeys under 400 m² upstairs, or 3 storeys under 500 m² |
| Lift sizeNZS 9.2 | 1400 × 1400 mm (1.4 m) car, 900 mm door, 1800 mm (1.8 m) clear in front | |
| Parking, seats and rooms | ||
| Accessible car parksD1 10.1.1 COMMENT · NZS Table 1 | Points to NZS 4121 | 1 up to 20, 2 up to 50, then 1 more per 50 |
| Accessible park widthNZS 5.5.1.1 | 3500 mm (3.5 m) | |
| Wheelchair spacesD1 8.1.1 · NZS 12.2.1.1 (a) | 2 up to 250 seats, then one more per additional 250 seats | 2 up to 250 people, then one more per 250 people or part |
| Accessible guest roomsD1 Table 9 · NZS Table 2 | 1 up to 10, 2 up to 25, then 1 more per 25 | 1 up to 10, 2 up to 25, then 1 more per 25 |
Where they differ
Ramp handrail heightD1/AS1 · NZS 4121
D1/AS1 wants handrails 900–1000 mm (0.9–1 m) above the pitch line on ramps as well as stairs (Figure 25 is headed for both). NZS 4121 wants ramp handrails at 840–900 mm. Only 900 mm works for both.
6.0.6, Figure 25, NZS 4121 6.4.2.6
When a lift is neededD1/AS1 · NZS 4121
Clause D1 counts people: a lift at 4 storeys or more, at 3 storeys with 50 or more on the two upper floors, and at 2 storeys with 40 or more upstairs. NZS 4121 measures floor area: no lift at 2 storeys if the upper floor is under 400 m², or at 3 storeys if the upper floors are under 500 m², but only if the ground floor meets NZS 4121 in full and people who can walk with difficulty can still get upstairs. D1/AS1 12.0.2 accepts either test, and they can disagree: a small upper floor with a lot of people can need a lift by head count and not by area, and a big quiet one the other way round. NZS 4121 also wants a lift to an upstairs public library or a place of assembly for 250 or more.
Clause D1.3.4(c), 12.0.1, 12.0.2, NZS 4121 9.1.3
How often a ramp needs a landingD1/AS1 · NZS 4121
D1/AS1 counts rise: a landing every 750 mm up. NZS 4121 counts run: a landing every 9000 mm (9 m) along. At 1 in 12 the two land in the same place. On a flatter ramp NZS asks sooner: at 1 in 14 it's every 9000 mm (9 m) of run against D1's 10500 mm (10.5 m). Sloping paths between 1 in 33 and 1 in 20 are footpaths to NZS 4121, with a rest area every 18 m; D1/AS1 still wants a landing every 750 mm of rise, which at 1 in 20 is every 15000 mm (15 m), so D1 asks more there. They swap over at 1 in 24.
Table 5, 3.3.1, NZS 4121 6.5.1, NZS 4121 6.2.2
Stair landing lengthD1/AS1 · NZS 4121
D1/AS1: 900 mm. NZS 4121: 1200 mm (1.2 m), mid-flight landings included, long enough for people to carry someone down the stairs in their wheelchair.
4.3.4, NZS 4121 8.3.6.1
Handrail extension at the bottomD1/AS1 · NZS 4121
D1/AS1: 300 mm past each end. NZS 4121: 300 mm at the top, and at the bottom 300 mm plus one going, so the level part starts at full handrail height. D1's Figure 25 looks as if it draws that extra length too, but 6.0.4 only says 300 mm.
6.0.4, Figure 25, NZS 4121 8.6.5.1
Open side of a rampD1/AS1 · NZS 4121
Both want a 75 mm upstand where a ramp has a drop. NZS 4121 adds a middle rail, at mid-height from the handrail down to the upstand or edge rail, so nobody slides out under the handrail.
3.1.3, NZS 4121 6.4.2.5
Small changes of levelD1/AS1 · NZS 4121
D1/AS1 lets a weather stop up to 20 mm stand. Anything more is a ramp to Section 3, which on an accessible route means 1 in 12; there's no short steep ramp in D1/AS1. NZS 4121 allows a 1 in 8 threshold ramp up to 450 mm long, and a 1 in 8 step ramp up to 1520 mm (1.52 m). So a short 1 in 8 ramp at a door meets NZS 4121 but not D1/AS1.
1.3.1, 1.3.2, Table 3, NZS 4121 7.1.4, NZS 4121 6.6.2
Counting wheelchair spacesD1/AS1 · NZS 4121
D1/AS1: 2 spaces up to 250 seats, then one more for every additional 250. NZS 4121: 2 up to 250 people, then one more for every 250 or part of it. Read as written they part between whole bands: from 251 to 499 seats D1/AS1 asks for 2 and NZS 4121 for 3. D1/AS1 counts seats and NZS 4121 people, so standing room counts too.
8.1.1, NZS 4121 12.2.1.1 (a), NZS 4121 12.2.1.1 (b)
Counting accessible guest roomsD1/AS1 · NZS 4121
Same numbers. NZS 4121 also counts cabins, tent sites and caravan sites, and says what counts as one unit: a motel unit, a hotel room or suite, or a dormitory bedroom.
Table 9, NZS 4121 Table 2, NZS 4121 14.5.1
Which doors need a vision panelD1/AS1 · NZS 4121
D1/AS1 asks for a vision panel only where a door swings both ways. NZS 4121 applies Figure 21's panel to doors on an accessible route: read one way that is every door on the route, read the other it only sizes the glass a glazed door already has. Neither document settles which, so a design that leans on NZS 4121 should say which reading it took.
7.0.4, Figure 28, NZS 4121 7.3.2 (c), NZS 4121 Figure 21
About the documents themselves
- Two acceptable solutions, not one on top of the otherBuilding Act 2004 s118, s119, NZS 4121 1.2
- NZS 4121 is an acceptable solution because Building Act s119 says so, for the access, parking and toilets s118 asks for in buildings the public uses. Following it is one way to comply, the same as following D1/AS1. NZS 4121 says (1.2) that some of it goes further than the Building Code. That's extra on the NZS route, not something D1/AS1 has to meet as well. Which one your consent authority expects is not something this page can tell you.
- Each sends you to the otherNZS 4121 4.5.6, 4.6.1, D1/AS1 10.1.1, 12.0.2
- NZS 4121 leaves projections and slip resistance to D1/AS1. D1/AS1 leaves accessible car parks and the lift-by-floor-area test to NZS 4121. So whichever you follow, you end up reading bits of the other.
- D1/AS1 12.0.1 points at documents that are goneD1/AS1 12.0.1
- To count a floor's occupancy for the lift test, 12.0.1 says to use C/AS2 to C/AS6 or C/VM2. C/AS3 to C/AS6 no longer exist; C/AS2 now covers everything but risk group SH, so that's where the occupant densities are.
- NZS 4121 gives two lengths for a kerb rampNZS 4121 1.5.1, 13.4.3.1 (b)
- Its definition says a kerb ramp is no longer than 1520 mm (1.52 m); 13.4.3.1 (b) says 1500 mm (1.5 m). Keep it to 1500 mm (1.5 m) and both are met.
- NZS 4121 is from 2001NZS 4121 1.4.2, Building Act 2004 s119(4)
- It still refers to the Building Act 1991 (s47A). The 2004 Act carries it over in s119, which also says the Minister must recommend adopting a new edition within 6 months of one being published. No new edition has come out.
D1 requirements
Every requirement D1 states, with the limit the stairway and ramp types choose, numbered so one can be pasted onto a sheet as it stands. Where the document states a condition, N/A answers that it does not hold here; the answer prints, so the sheet says what was left out and why. The values worked out from a design are on its own face; the reading and the guidance do not print.
Stairways
The stairway type chooses the row of Table 6 and Table 7 each limit is read from.
where there is a stairway4.0
Stairway type
A private stairway between frequently used spaces: living areas, kitchens, garages. All exterior private stairways are main private. Definitions, pp.14–16
- Riser height No more than 190 mm for Main private stairways.
4.1.1, Table 6
- Tread depth No less than 280 mm for Main private stairways, measured to the front of the nosing.
4.1.1, Table 6
- Pitch line slope No steeper than 37° for Main private stairways.
4.1.1, Table 6, Figure 11
- Rise between landings No more than 4000 mm (4 m) between successive landings for Main private stairways.
4.3.2, Table 7
- Landing size No less than 900 mm long, and no narrower than the access route it serves.
4.3.3, 4.3.4
- Line of sight Where landings are more than 8000 mm (8 m) apart vertically, the line of sight between them is broken: offset the flights, turn one by at least 30°, or use a landing at least 1800 mm (1.8 m) long.
4.3.6
- Nosings A tread projects no more than 25 mm past a closed riser. With open risers, each tread overlaps the one below by 15–25 mm.
4.1.6, Figure 12
- Uniformity Riser height and tread depth are uniform within ±5 mm through each flight, measured at the centreline on straight flights and at the pitch line on curved and spiral flights.
4.1.3
- Landings Landings are provided at the top and bottom of every flight, and where a door opens into the stairway.
4.3.1
- Landings clear of obstruction Landings are clear of permanent obstruction, with at least 400 mm across the full landing width beyond the arc of any opening door.
4.3.5, Figure 15
- A door at a short flight Where the rise of a flight is no more than 600 mm and the door slides or opens away from the steps, no landing is required between the flight and the door.
4.3.1, Figure 14
- Pitch line on tapered treads The pitch line of a curved or spiral stairway with tapered treads runs 300 mm in from the handrail on a spiral stairway narrower than 1000 mm (1 m), and 300 mm in from each side on a curved stairway 1000 mm (1 m) wide or more.
4.4.1, Figure 17
- Tapered treads Consecutive tapered treads have a uniform taper angle, and the pitch line slope, riser height and tread depth along both pitch lines meet Table 6 and Figure 11.
4.4.2, Table 6, Figure 11
- Narrow spiral stairways A spiral stairway narrower than 1000 mm (1 m) serves only as a private or service stairway.
4.4.1 a), Figure 17(a)
- Winders Winders only on private and service stairways, and only where the riser and tread on the pitch line meet Table 6 and Figure 11, the riser is uniform and the same as on the straight flights either side, the tread on the pitch line is no less than on those flights, the winders have a uniform taper angle, and consecutive winders turn through no more than 180°.
4.5.1, Table 6, Figure 11
- Pitch line on winders The pitch line at the middle of a stairway narrower than 1000 mm (1 m), and 300 mm in from each side of one 1000 mm (1 m) wide or more.
4.5.2, Figure 18, Figure 17(b)
Ramps
where there is a ramp3.0
Type of ramp
On an accessible route. Carries the upstand and clear width requirements of 3.1.3 and 3.2.
- Slope No steeper than 1 in 12 for Accessible ramps.
3.1.1, Table 3
- Rise between landings For a ramp steeper than 1 in 33, intermediate landings at no more than 750 mm of rise.
3.3.1, Table 5
- Landing length No less than 1200 mm (1.2 m).
3.3.3, Table 5
- Upstand No less than 75 mm on any drop-off side of the ramp.
3.1.3, Figure 9
- Clear width The clear width of an accessible ramp is 1200 mm (1.2 m).
3.2
- Ramp landings Ramp landings are level and clear, and landing width is no less than the minimum width of the ramp they serve.
3.3.2, 3.3.3
- Ramp surface The ramp surface is a slip resistant surface complying with Table 2.
3.1.4, Table 2
Fixed ladders
where there is a fixed ladder5.0
- Where a rung-type ladder does not go No rung-type ladder where access is frequent and tools, equipment or materials are carried.
5.1.1
- Nobody underneath A fixed ladder within an access route placed so that nobody working or walking beneath it is endangered while it is climbed.
5.1.3
- Ladder landings Landings no narrower than the ladder they serve, and as long as it is wide, or longer where 5.1.7 asks.
5.1.4, 5.1.5
- Even spacing Rungs or treads spaced uniformly within ±5 mm through the whole ladder installation.
5.1.6
- Safety hoops Protection from falling from a ladder that rises more than 6 m above the ground or rises from a landing or platform: safety hoops and longitudinal straps of 50 × 8 mm grade 250 steel, the hoops no more than 1000 mm (1 m) apart, the highest level with the top of the barrier on the platform reached and the lowest 2.5 m above the ground or platform.
5.1.2
- Hoop dimensions Hoops dimensioned as Figure 21: rectangular, 700 to 750 mm across and deep, with corners of at least 150 mm radius; or circular, of 350 to 400 mm radius and 750 to 850 mm deep, with at least 400 mm open at the ladder.
5.1.2 b), Figure 21
- Arresting a fall An installation of more than one ladder section, more than 6 m high in all, has as well as its hoops a change of direction between successive ladders at each landing, successive ladders offset at each landing, or landings at least 1.5 m long.
5.1.7, 5.1.5
- Step-type ladders A slope of 60° to 70° from the horizontal; treads at least 100 mm wide, evenly spaced at 200 to 250 mm centres; at least 450 mm between the stiles; and no more than 6 m between landings.
5.2.1, Figure 19
- Step-type clearances At least 50 mm for the hand along the handrail and 50 mm between the treads and any solid object behind the ladder, and horizontal openings at landings of at least 1150 mm (1.15 m).
5.2.1 e), 5.2.1 f)
- Step-type handrails Handrails on both sides, 550 to 750 mm apart, no more than 450 mm above the stile, starting no lower than 900 mm above the floor, running at least 900 mm above the upper landing to meet any barrier, and built to 6.0.1 to 6.0.6.
5.2.1 g)
- Rung-type ladders A pitch line slope of 70° to 90° from the horizontal; rungs at least 20 mm in diameter, evenly spaced at 250 to 300 mm centres; 350 to 500 mm between the stiles; and no more than 9 m between landings.
5.3.1, Figure 20
- Rung-type clearances At least 750 mm between the rungs and any obstruction behind the climber, 300 mm from the ladder's centre line to each side, 50 mm for the hand along stiles that run above a landing, and 200 mm between the rungs and any solid object behind the ladder.
5.3.1 e)
- Getting off a rung-type ladder Stiles running to the height of the barrier and at least 900 mm above the landing, and no toeboard across the ladder opening. For step-through access, stiles 500 to 700 mm apart above the landing and the top rung level with it or one full rise below; for side access, 150 to 300 mm from the nearest stile to the landing and the top rung level with it.
5.3.2, Figure 22, Figure 23
- Individual rungs Rungs at least 25 mm in diameter, shaped so a foot cannot slip off sideways, evenly spaced at 250 to 350 mm centres; a tread on each rung 300 to 550 mm wide, or at least 200 mm where the rungs are staggered; and a rung-type ladder's height of no more than 9 m between landings, and its clearances.
5.4.1, Figure 24
Handrails
- Height Between 900 mm and 1 m above the pitch line, measured to the top of the handrail.
6.0.6, Figure 25
- Slope and length The same slope as the pitch line, beginning no further than the second riser from the lower end, and extending the full length of the stairway it serves.
6.0.4
- Under the handrail D1 only sets the handrail. What fills the side below it is F4/AS1's. Where someone could fall 1 m or more, the side needs a barrier. In housing, or anywhere children under 6 are likely, no gap in it may let a 100 mm sphere through, and the triangle between the tread, riser and bottom rail must not let a 150 mm sphere through. Elsewhere, gaps may be up to 300 mm between balusters or 460 mm between rails. F4/AS1 Figures 1–4 show barriers a small child can't easily climb. On Stairways.
NZBC F4.3.1, F4/AS1 1.2.1, 1.2.2, Figures 1–4
- Extensions A horizontal extension of at least 300 mm at each end. Extensions may be turned down rather than ended abruptly, and the first riser sits far enough back from the corner to accommodate one. On Ramps.
6.0.4, Figures 9 and 25
- Under the handrail D1 only sets the handrail. What fills the side below it is F4/AS1's. Where someone could fall 1 m or more, the side needs a barrier. In housing, or anywhere children under 6 are likely, no gap in it may let a 100 mm sphere through. Elsewhere, gaps may be up to 300 mm between balusters or 460 mm between rails. F4/AS1 Figures 1–4 show barriers a small child can't easily climb. On Ramps.
NZBC F4.3.1, F4/AS1 1.2.1, 1.2.2, Figures 1–4
- Handrail profile Handrail profiles can be readily grasped by an adult hand.
6.0
Barriers
- Barrier on the stair No less than 900 mm, measured vertically from the pitch line or the nosings. F4/AS1 Table 1, Detached dwellings and within household units of multi-unit dwellings: Stairs and ramps and their intermediate landings. On Stairways.
F4/AS1 Table 1, F4/AS1 Table 1 Note 1
- Barrier at the floor edge No less than 1000 mm (1 m) where the stair meets a floor edge, measured from finished floor level. F4/AS1 Table 1, Detached dwellings and within household units of multi-unit dwellings: Balconies and decks, and edges of internal floors or mezzanine floors.
F4/AS1 Table 1, F4/AS1 Table 1 Note 1
- Handrail on the barrier Where a handrail is mounted on top of a stairway barrier, it may transition up to 1100 mm (1.1 m) on the intermediate landings. On Stairways.
F4/AS1 Table 1 Note 5
- Barrier on the ramp No less than 900 mm, measured vertically from finished floor level. F4/AS1 Table 1, Detached dwellings and within household units of multi-unit dwellings: Stairs and ramps and their intermediate landings. On Ramps.
F4/AS1 Table 1, F4/AS1 Table 1 Note 1
Accessible route
Clause D1.3.2 asks for a route people with disabilities can use, and sets out the buildings it does not reach. A house is one of them; a block of flats, a shop and an office are not.
where Performance D1.3.2 applies: the building is not Housing, an Outbuilding, a backcountry hut, an Ancillary building, or an Industrial building where no more than 10 people are employedClause D1.3.2, limits on application
- The route An accessible route is continuous, can be negotiated unaided by a wheelchair user, and runs from the street boundary or car parking area to the spaces within the building required to be accessible.
Definitions, Accessible route
- Clear width No less than 1200 mm (1.2 m) along an accessible route.
2.2.1
- Edge of an accessible route Where an accessible route is more than 25 mm above the adjacent ground, a 75 mm upstand or a low barrier rail is provided.
2.3.1
- Kerb ramps Kerb ramps have a slope no greater than 1 in 8, and colour and texture contrast with the adjacent footpath.
3.4.1
Doors
Risk group, for the escape route figures
Escape route figures are C/AS1's for risk group SH and C/AS2's for every other group. Set the classified use on the project, or pick the group here.
- Clear opening Accessible doors have a clear opening of at least 760 mm.
7.0.3
- Swing and height Opens no less than 90°, and the opening has a clear height of no less than 1955 mm (1.955 m) for the required width. The door swing must not obstruct the minimum required width of the escape route.
C/AS1 3.2.4.1 b), C/AS1 3.2.4.1 c), C/AS2 3.9.4.5(a), C/AS2 3.9.4.5(c), C/AS1 3.2.1 b), C/AS2 3.2.1.1(b)
- Space beside the handle Where a person must open the door towards the wheelchair, an unobstructed wall space of no less than 300 mm at the handle side.
7.0.1, Figure 27 (b)
- Handle height Between 900 mm and 1200 mm (1.2 m) above floor level, lever action, openable with one hand, with the handle end returned towards the door.
7.0.5
- Contrast Accessible doors are of a colour that contrasts with their surroundings.
7.0.4
- Doors swinging both ways Doors that swing in both directions incorporate glazing that gives a person using the door adequate visibility, as Figure 28 shows.
7.0.4, Figure 28
- Revolving doors and turnstiles Where revolving doors or turnstiles are used within an accessible route, an alternative hinged or sliding door is provided.
7.0.6, Figure 29
- Frameless glass doors Frameless glass doors comply with NZBC F2.
7.0.7, NZBC F2
Places of assembly
where there are rooms or areas used for public meetings, entertainment or assembly8.1.1
- Wheelchair spaces 2 spaces for wheelchairs where there are up to 250 seats, and 1 more for every additional 250 seats.
8.1.1
- Where they are The wheelchair spaces immediately next to other seating, as Figure 30 shows.
8.1.2, Figure 30
- The stage An accessible route to the podium or stage.
8.2.1
Accessible accommodation units
where the building is a hotel, motel or other Communal Residential building that provides accommodation for the public9.1.1
- How many Accessible accommodation units in hotels, motels and other Communal Residential buildings that house the public, at least as Table 9 gives: 1 for up to 10 guest units, 2 for up to 25, and 1 more for every additional 25.
9.1.1, Table 9
- What each one has Toilet and bathroom facilities that comply with G1/AS1; bedrooms, sitting and dining areas with clear floor for a 1500 mm (1.5 m) turning circle; and an accessible kitchen or accessible tea and coffee making facilities, in line with what the building's other units have.
9.2.1
Escape routes
where a stairway, ramp or ladder is part of an escape routeC/AS1 3.1.1.1, C/AS2 3.1.1.6
Risk group, for the escape route figures
Escape route figures are C/AS1's for risk group SH and C/AS2's for every other group. Set the classified use on the project, or pick the group here.
- D1 on an escape route Ramps, stairs, ladders, landings, handrails, doors, vision panels and openings on an escape route meet D1/AS1.
C/AS1 3.1.1.1, C/AS2 3.1.1.6
- Stairs and ladders in an open path, C/AS1 A stair in an open path counts as its plan length measured on the stair's centreline plus the plan length of each landing, and a ladder as its vertical height.
C/AS1 3.3.2.1 c), C/AS1 3.3.2.1 d)
- Stairs and ladders in an open path, C/AS2 A straight or curved stair in an open path counts as its plan length on the centreline times 1.2, plus the plan length of each landing; a spiral stair as 2 times its vertical height; and a ladder as 3 times its vertical height.
C/AS2 3.3.4.1
- Handrails in the width A handrail that meets D1/AS1 may project no more than 100 mm into the width of an escape route.
C/AS1 3.2.3.1 a), C/AS2 3.2.4.1(b)
- Curved and spiral stairs A curved or spiral stair on an escape route has its required width measured across the treads where their depth meets D1/AS1's tread depth.
C/AS2 3.2.3.3
- Ladders as escape routes A ladder as an escape route only from a dead end, for risk groups other than SM and SI, where it serves only support activities and the occupant load does not normally exceed 4. Nowhere else.
C/AS2 3.4.10.3, C/AS2 3.4.10.4
Access routes and clearances
- Height clearance Height clearances along every access route comply with Table 1, as Figure 3 shows them.
1.4.1, Table 1, Figure 3
- Minor projections A minor projection is only permitted at all if it is designed to minimise the risk of injury or impact.
1.5.1
Slip resistance
- Walking surfaces Slip resistance by 2.1.2 to 2.1.5: a surface Table 2 accepts for the situation, or the AS 4586 test method those paragraphs name.
2.1.2, 2.1.3, 2.1.5, Table 2
- Wet to dry transition The transition zone between the part of an access route intended to remain dry and the part that may become wet is provided with absorbent matting, an extension of the wet slip resistant surface, or both.
2.1.6
Stairway lighting
- Light at the treads At least 100 lux at tread level for private and service stairways.
4.6.1, Table 8 Notes
- Light on the route At least 20 lux at floor level along the access route, landings and lobbies included.
NZBC G8.2 b), G8.3, G8/VM1
- Switches Except on external private stairways, stairway lighting switches can be activated at the top, at the bottom, and at any intermediate landing having access to or from a floor.
4.6.2
D1 requirements to show on the drawings
What has to be drawn or named for each requirement and value to be checkable. It follows the answers on Requirements. Tick as you go; the ticks print, the guidance does not.
Stairway: Main private. Ramp: Accessible. Escape routes: risk group not given.
Show on the drawings
- 4.1.1, 4.1.3, 4.1.6, Table 6, Table 7
- 4.3.1, 4.3.4, 4.3.5, 4.3.6
- 4.4.1, 4.4.2, 4.5.1, 4.5.2, Figures 17 and 18
- 4.2.1, 3.2
- 6.0
- F4/AS1 Table 1, F4/AS1 1.2.1, F4/AS1 1.2.2
- Table 3, Table 5, 3.1.2, 3.1.3
- 5.1.1, 5.1.6, 5.2.1, 5.3.1, 5.4.1
- 5.2.1 e), 5.3.1 e), 5.1.3
- 5.1.4, 5.1.5, 5.2.1 g), 5.3.2
- 5.1.2, Figure 21
- 5.1.7
- Definitions, Accessible route, 2.2.1
- 2.3.1
- 3.4.1, Figure 10
- 7.0.1, 7.0.3, 7.0.4, 7.0.5
- C/AS1 3.2.4.1 b), C/AS1 3.2.4.1 c), C/AS2 3.9.4.5(a), C/AS2 3.9.4.5(c), C/AS1 3.2.1 b), C/AS2 3.2.1.1(b)
- C/AS1 3.1.1.1, C/AS2 3.1.1.6, C/AS1 3.3.2.1 c), C/AS1 3.3.2.1 d), C/AS2 3.3.4.1
- C/AS1 3.2.3.1 a), C/AS2 3.2.4.1(b)
- C/AS2 3.2.3.3
- C/AS2 3.4.10.3, C/AS2 3.4.10.4
- 7.0.4, Figure 28
- 7.0.6, Figure 29
- 7.0.7, NZBC F2
- 8.1.1, 8.1.2, Figure 30
- 8.2.1
- 9.1.1, Table 9
- 9.2.1
- 1.4.1, Table 1, 1.5.1
- 2.1.2, 2.1.5, 3.1.4, Table 2
- 2.1.6
- 4.6.1, 4.6.2, Table 8
Terminology
The stairway and ramp types are definitions in the document rather than judgements about the building, and the limits turn on them entirely.
- Service (stairway)Definitions, pp.14–16
- Used infrequently by service personnel to reach spaces for maintenance and the movement of goods.
- Minor private (stairway)Definitions, pp.14–16
- A private stairway off the main thoroughfare, giving infrequent access to a single room that is not a living area.
- Secondary private (stairway)Definitions, pp.14–16
- A private stairway that is neither main nor minor, reaching a floor containing only bedrooms, a bathroom or similar.
- Main private (stairway)Definitions, pp.14–16
- A private stairway between frequently used spaces: living areas, kitchens, garages. All exterior private stairways are main private.
- Common (stairway)Definitions, pp.14–16
- Used by the public, whether as of right or not, and not private, service or accessible.
- Accessible (stairway)Definitions, pp.14–16
- On an accessible route: a route a person with disabilities can negotiate, extending from the street boundary or car park to the spaces required to be accessible.
- Accessible (ramp)Table 3, 3.1.1
- On an accessible route. Carries the upstand and clear width requirements of 3.1.3 and 3.2.
- Common, subject to wetting (ramp)Table 3, 3.1.1
- A ramp used by the public that can get wet: external, or otherwise exposed.
- Common, normally dry (ramp)Table 3, 3.1.1
- A ramp used by the public that stays dry in normal use.
- Service (ramp)Table 3, 3.1.1
- Used infrequently by service personnel for maintenance and the movement of goods. Steep enough to need footholds beyond 1 in 8.
- Pitch lineDefinitions p.15, 4.1.1
- The line joining the nosings of successive treads. Its slope, riser over tread on a uniform flight, is what Table 6 limits and what a handrail follows.
- Accessible routeDefinitions, pp.14–16, 2.0
- A route a person with disabilities can negotiate, extending from the street boundary or car park to the spaces required to be accessible. Doors, ramps and stairways on it carry the accessible requirements.
Reading D1
Why the documents read as they do. Screen only; none of it is a note.
- Table 6 and Table 7 do not share a list of stairwaysTable 6, Table 7, Definitions, pp.14–16
- Table 6 splits private stairways into main, secondary and minor; Table 7 does not. All three are defined as private stairways (Definitions, pp.14–16), which is how they are mapped to Table 7's Private row here. Neither table states it.
- The gait comment under 4.1.14.1.1 COMMENT, Figure 2
- Below 23° a stair does not allow an acceptable gait, and broken rhythm is where dangerous falls happen. A comment on 4.1.1, not a requirement: noted beside a design, never counted against it.
- D1 and G8 price the same room differentlyTable 8 Notes, G8/AS1 Table 1 Note 4, G8/VM1 1.0.3
- D1/AS1 Table 8 and G8/AS1 Table 1 both work from the same room: a 7 m × 4 m stair lobby. G8 wants 20 lux on the floor; D1 wants 100 lux (private and service stairs) or 150 lux (accessible and common) at the treads. Divide the light by the watts and they don't agree: for the same kind of fitting, D1 gets 2.4 to 3.8 times as much light from each watt as G8 does. Neither document says why. Our guess: G8's 20 lux is the dimmest spot on the floor (G8/VM1 measures the low points), while D1's reads like an average. Either way, don't scale one table to get the other. Use G8 for the lobby and D1 for the treads.
Stairways
- Spiral stairways1.4.1 COMMENT
- 1.4.1's COMMENT: take particular care over the height clearance between the pitch line and the underside of an upper tread where spiral stairways are used. The clearance itself is Table 1's.
- An accessible curved stairwayFigure 17(b)
- Figure 17(b) accepts a curved stairway 1000 mm (1 m) wide or more as an accessible stairway where it has handrails on both sides.
- Another route for spiral stairways4.4.1, 4.4.1 COMMENT 2
- BS 5395 Part 2 is an acceptable solution for a spiral stairway no less than 1500 mm (1.5 m) in diameter. The COMMENT adds that a smaller one built to it may serve as an additional way to a space that other access routes already serve well.
- Why the lines are where they are4.4.1 COMMENT 1
- The COMMENT explains Figure 17: people are taken to walk up and down only on the outside of a narrow stairway, and on both the inside and the outside of a wider one.
- Another route for winders4.5.3
- BS 585 Part 1 is an acceptable solution for winders on stairways 770 to 1200 mm (1.2 m) wide.
- Most risers, by slope1.2.1, Figure 2, Table 6
- Up to 30 risers before this stops being a stairway: Figure 2 draws the line between a ramp and a stair at 18°, and at 30 risers with the 280 mm minimum tread the pitch is 18.16°. Beyond that no tread brings it back above 18°.
- Width4.2.1 COMMENT
- D1/AS1 sets no minimum width for a stairway within a household unit. Its comment points at C/AS2 3.3.2's 850 mm for risk group SM as a practical minimum for any private stairway, and notes that narrower stairs make moving furniture difficult.
Ramps
- A figure, not a minimum3.2, 2.2.1
- 3.2 states the clear width of an accessible ramp as 1200 mm (1.2 m), not as a minimum, where 2.2.1 words an accessible route's as no less than 1200 mm (1.2 m). A ramp on an accessible route is part of that route.
- Glazed and polished ramps3.1.4 COMMENT 2
- 3.1.4's COMMENT: glazed or polished walking surfaces are normally unsuitable for common ramps (see Table 2's notes).
Fixed ladders
- Choosing a ladder5.1.1 COMMENT 1
- The COMMENT asks for thought about why access is needed, how often, and whether tools or materials are carried by hand. It says a rung-type ladder does not suit the way to a lift machine room or plant room visited at least monthly with tools or materials, and does suit roofs, pits, silos, towers, chimneys and tanks reached infrequently.
- Ladders in Housing5.1.1 COMMENT 2, 5.1.1
- The COMMENT accepts ladders in Housing to reach spaces used infrequently, such as attics and lofts. BS EN 14975 is an acceptable solution for retractable loft and attic ladders in housing, and for maintenance access in other buildings.
- The barrier Figure 20 drawsFigure 20, 11.0.1 COMMENT, F4/AS1 Table 1
- Figure 20 draws the barrier at the top of a rung-type ladder 1000 mm (1 m) high. 11.0.1's COMMENT says a barrier of that height is to be treated as an alternative solution to F4/AS1 Table 1, whose height for places outside housing is 1100 mm (1.1 m). So a barrier built to the drawing's height is an alternative solution, not D1/AS1's.
- Another route for service access11.0.1
- AS 1657 is an acceptable solution for the stairs, ladders, platforms and walkways that service and maintenance people use.
Handrails
- Two units for one range6.0.6
- 6.0.6 writes the lower bound as 900 mm and the upper as 1 m: one range in two units, 900 to 1000 mm (1 m).
Places of assembly
- Counting by people8.1.1, NZS 4121 12.2.1.1
- NZS 4121 counts the people a room holds, standing room included, and adds a space for part of a band as well as a whole one, so between whole bands it asks for one more. Seats and rooms works both counts for one room.
Accessible accommodation units
- Kitchens9.2.1 COMMENT
- The COMMENT points to MBIE's guidance on accessible units in public accommodation. The G3 page works an accessible kitchen, NZS 4121's figures included.
Access routes and clearances
- Car parks10.1.1, 10.1.1 COMMENT
- AS/NZS 2890 Part 1 is an acceptable solution for car parks and the routes through them. The COMMENT sends accessible parking, and how many parks there are to be, to NZS 4121 Section 5, which the NZS 4121 page works.
- Loading spaces11.0.2, References
- 11.0.2 names AS 2980 Part 2 as an acceptable solution for loading spaces and routes for commercial vehicles. The document's References list gives AS/NZS 2890 Part 2, off-street commercial vehicle facilities, for 11.0.2, so the number in the paragraph reads as a slip. Neither standard is held here.
Slip resistance
- Durability of the surfaceTable 2 Note 12, NZBC B2
- Table 2's Note 12: to meet NZBC B2, a walking surface should have at least a 5 year life under normal maintenance. A should in a table note, so it is read here rather than listed; the requirement itself is B2's, and B2's periods are on the B2 page.
Where the rest is
What this page reads, and what it points at rather than reads.