E3/AS1 Internal Moisture

What internal moisture puts on a set of drawings: the impervious finishes and the evidence for one the document does not list, the thermal resistance and condensation control of Section 1.0, containment and floor wastes where an overflow could reach somebody else, and the shower.

  • E3/AS1Second Edition Amendment 75 Nov 2020
  • E3/AS2First Edition5 Nov 2020
  • G13/AS1Second Edition Amendment 102 Nov 2023
  • WMAI Code of Practice
  • GIB Wet Area Systems
  • Building Act 2004

E3 requirements

Every requirement E3 states, numbered, so one can be pasted onto a sheet as it stands. Where the document states a condition, N/A answers that it does not hold here; the answer prints, so the sheet says what was left out and why. The reading and the guidance do not print.

Finishes, and the evidence a finish outside E3 needs

The question that arrives at consent is usually not what the Code says but what has to be submitted. E3/AS1 lists three floor finishes and four wall finishes, and most designs use something else.

  1. Floor finishes E3/AS1 accepts Integrally waterproof sheet material with sealed joints, sealed or coved at edges where watersplash may occur. Or ceramic or stone tiles of no more than 6% water absorption, waterproof grouted joints, bedded with an adhesive the tile manufacturer specifies for the tiles, the substrate and the environment, edges sealed or coved where watersplash may occur, laid on a continuous impervious substrate or a membrane the manufacturer specifies as suitable.

    3.1.1 a), 3.1.1 b)

  2. Sealed concrete, in two places only A slab-on-grade concrete floor with a steel trowel or polished finish, sealed at edges where watersplash may occur, satisfies 3.1.1 in a domestic laundry within a garage or in a building containing only sanitary facilities. Nowhere else.

    3.1.1 c)

  3. Wall finishes E3/AS1 accepts Integrally waterproof sheet with sealed joints; or ceramic or stone tiles of no more than 6% water absorption on a specified adhesive; or sheet linings with a semi-gloss or gloss coating, or a hard-wearing low-sheen latex paint containing mould inhibitors; or water resistant sheet linings finished with decorative high pressure laminate or factory-applied polyurethane or resin, with impervious joints.

    3.1.2 a), 3.1.2 b), 3.1.2 c), 3.1.2 d)

  4. Where the impervious floor extends to Throughout any space containing sanitary fixtures or sanitary appliances, and in an open plan space at least 1500 mm (1.5 m) from every one of them. Tiles in that band bring 3.1.1 b)'s substrate or membrane with them.

    3.1.1

Section 1.0: thermal resistance, ventilation and condensation

E3.3.1 reaches only Housing and Communal Residential; Sections 2.0 and 3.0 reach every building. A detached house, a flat and a boarding house are all on this side.

where the building is Housing or Communal ResidentialClause E3.3.1, limits on application

  1. Minimum R-values No less than R1.5 for a framed wall with a cavity, R0.6 for a single-skin normal-weight masonry wall without a cavity, R0.6 for a solid timber wall no less than 60 mm thick, and R1.5 for a roof or ceiling of any construction.

    1.1.1

  2. How the R-value is determined By the methods in NZS 4214. A laboratory test sample must be truly representative of the wall, roof or ceiling system, including any provision for reducing thermal bridging.

    1.1.2, NZS 4214

  3. Building paper Extends from the upper side of the top plate to the underside of the bearers or wall plates supporting the ground floor joists.

    1.1.4 a)

  4. Insulation fit No perimeter gaps between the insulating material and the framing members.

    1.1.4 c)

  5. Thermal break to steel framing Where steel framing is used, a thermal break with a minimum R-value of R0.25 at the outside face of each steel framing member. EPS strips 10 mm thick provide it; other materials or methods may, if they provide the same minimum.

    1.1.4 d)

  6. Foil insulation Where foil insulation is used, it is placed on the lining side of the studs, not the cladding side.

    1.1.4 e)

  7. Ventilation Provided naturally or mechanically to comply with G4/AS1.

    1.2.1, G4/AS1

  8. Condensation channels Metal-framed windows with single glazing, in a building that is not air conditioned, have a means of condensation disposal: a collection channel of clear dimensions no less than 10 mm wide by 5 mm deep, which either drains to the outside or holds the water until it evaporates.

    1.3.1, 1.3.3

  9. Channel ends and outlets Channels have closed ends and no openings that let ponded water reach building elements susceptible to moisture. Drainage outlets can expel all condensed water and prevent it being blown back by wind pressure.

    1.3.2

  10. Cleaning Channels and drainage outlets can be cleaned.

    1.3.3

Section 2.0: overflow

A detached house on its own lot has nowhere for an overflow to reach. Anything with a household unit above, below or beside another, or a fixture near a boundary, has. The requirement follows the fixture, not the room.

where a sanitary fixture is located where an accidental overflow could damage an adjoining household unit or other property2.0.1

  1. Overflow, Section 2.0 Containment and a floor waste are required at any sanitary fixture located where accidental overflow could damage an adjoining household unit or other property. The requirement follows the fixture's position, not the room it is in.

    2.0.1

  2. Containment An impervious floor covering, continuous and coved or with sealed joints where it meets the wall, extending to the doorway and all walls of the room, or at least 1500 mm (1.5 m) from every sanitary fixture and appliance in an open-plan room.

    2.0.1 a), 2.1.1, Figure 1

  3. Floor waste A floor waste complying with Clause G13, at each of those fixtures. A graded floor is not essential in this situation.

    2.0.1 a), 2.2.1, G13/AS1 3.4

  4. Floor waste diameter The floor waste, and its water trap if it has one, no less than 40 mm in diameter.

    G13/AS1 3.4.2

  5. Grating A removable grating, flush with the floor.

    G13/AS1 3.4.1

  6. How it discharges Trapped, discharging above a gully trap grating and vented; or trapped, charged to keep its water seal, and discharging to the foul water plumbing; or (where its only purpose is accidental overflow) untrapped, discharging to the open air within the property boundary at a safe location, with a means to keep out birds and vermin.

    G13/AS1 3.4.3

  7. Sinks and laundry tubs are exempt on a condition A household kitchen sink or laundry tub with an integrated overflow of no less than 0.25 L/s needs no containment or floor waste, provided the taps cannot outrun it: either the maximum tap flow is lower, or the supplies carry proprietary flow restrictors that make it so. The overflow is tested and verified to BS EN 274. Where several tubs or sinks share one tap, each has its own complying overflow, or a secondary one has a controlled overflow path into a main one that does. The exemption is that fixture's. A basin or WC beside it is still 2.0.1's.

    2.0.1 b), 2.0.2, 2.0.2.1, BS EN 274

  8. Appliance hoses are not an overflow Containment and a floor waste are not required solely for the failure of a dishwasher's or washing machine's component or hose, where the flexible discharge hose is directly connected into the plumbing system: mechanically fastened to a fixture trap spigot, or inserted into an open standpipe or a laundry tub waste hose connection port.

    2.0.3

The wet-area build-up: surfaces, joints and membrane

  1. Fixture to floor Where a sanitary fixture abuts the impervious floor finish, the base of the fixture is sealed to it.

    3.2.1

  2. Fixture to wall Where a bath, basin, tub or sink abuts an impervious lining, the joint between fixture and lining is sealed so water cannot reach concealed spaces or get behind the lining.

    3.2.2, Figure 3

  3. The membrane system Selection, design and installation to sections 1 – 4 of the Code of Practice, as modified.

    E3/AS2 1.1

  4. The finish over the membrane The membrane is installed with an over-surface finish that is easy to clean, forming the floor and wall surfaces at the fixtures. The finish itself (tiling, say) is outside E3/AS2, so its compliance is shown another way; E3/AS1 3.1 is the usual route.

    E3/AS2 1.1, E3.3.3 – E3.3.5, E3/AS1 3.1

Showers, and showers over baths

Sectionimpervious liningroseenclosure1800above shower floor300above rose1:50 fall to wastePlan, no enclosurewallroseR1500radius from the rose
Shower heights and the unenclosed radius, drawn from E3/AS1 3.3. Not to scale, and screen only.

where there is a shower3.3.1

  1. Lining height Impervious wall linings or finishes to 1800 mm (1.8 m) above the shower floor, and to 300 mm above the shower rose, whichever is higher.

    3.3.1, Figure 5(b)

  2. On the membrane route the height is the Code of Practice's E3/AS2 1.2 d) says the IWAM Code of Practice takes the membrane higher above the shower rose than the Building Code requires. E3/AS1's 50 mm is the Code minimum; the membrane is built to the Code of Practice's figure.

    E3/AS2 1.2 d)

  3. Top edge The top edge of the impervious shower wall lining or finish is sealed to the wall behind, or to the ceiling if full height, so condensation cannot get behind it.

    3.3.1

  4. Penetrations Tapware, mixers and roses through the shower wall are waterproofed with a proprietary flange system or with sealant, installed so they stay accessible for replacing washers, ceramic discs and o-rings.

    3.3.1, Figure 6

  5. Where the shower materials apply Within the shower enclosure; or, where there is no enclosure such as a wall, screen, door or curtain, within a 1500 mm (1.5 m) horizontal radius of the shower rose.

    3.3.1.1, 3.3.1.2, Figure 5

  6. Shower floor A plastic or stainless steel shower tray; or integrally waterproof sheet material with sealed joints, coved at edges; or ceramic or stone tiles of no more than 6% water absorption on a specified adhesive, laid within a tray the manufacturer specifies for tiles or on a membrane it specifies as suitable. A tiled shower floor must have tiled walls.

    3.3.1.1 a), 3.3.1.1 b), 3.3.1.1 c)

  7. Shower walls Plastic shower wall liners, jointless or with waterproof joints; or integrally waterproof sheet with sealed joints; or tiles of no more than 6% water absorption laid on a specified membrane; or water resistant sheet linings finished with high pressure laminate or factory-applied polyurethane or resin, with impervious joints.

    3.3.1.2

  8. Tray to wall Where a shower tray is used, the junction between tray and wall linings is detailed so the lining laps into the tray.

    3.3.2.2, Figure 4

  9. Shower over a bath The bath rim is no less than 15 mm high, and the shower wall lining laps over and is sealed to it. Either the rim is recessed into the wall framing or the lining is packed out to suit it. No bath mould or flashing.

    3.3.1.3

  10. Enclosure Where a wall, screen, door or curtain is used, it is continuous from floor level or the top of the upstand to no less than 1800 mm (1.8 m) above floor level, and to 300 mm above the rose on these drawings; 3.3.2.1 states 50 mm above the rose.

    3.3.2.1

  11. Floor fall Where the shower floor has no upstand, or a wall, screen, door or curtain is omitted, the floor falls no less than 1:50 towards the floor waste, across the area within a 1500 mm (1.5 m) radius of the point vertically below the rose, or from any wall within that radius.

    3.3.2.3, Figure 5

  12. Threshold A shower installed for use by people with disabilities has a level threshold.

    3.3.2

Urinals

where there is a urinal3.3.3

  1. Urinal Impervious wall extending horizontally at least 300 mm beyond each side of the urinal, and vertically from floor level to 1500 mm (1.5 m).

    3.3.3

Taking the E3/AS2 route

Usually yes: E3/AS1 governs the finished surface and E3/AS2 the membrane behind it, and a tiled shower wall needs a membrane under 3.3.1.2 c) whatever route is claimed. An acrylic liner over a vinyl floor may have none.

where a membrane system is built to the Code of Practice, under E3/AS2E3/AS2 1.1

  1. What it does not cover E3/AS2 cannot show compliance with E3.3.1. Thermal resistance, ventilation and condensation control are shown separately, and Section 1.0 above is E3/AS1's.

    E3/AS2 Supporting information, E3/AS1 1.0

This tool reads E3/AS1 Second Edition Amendment 7, effective 5 November 2020, and E3/AS2 First Edition, and lists what they put on a set of drawings. It reads G13/AS1 3.4 for the floor waste outlet only, and nothing of the WMAI Code of Practice. It is not a substitute for reading the documents, for the judgement of a suitably qualified person, or for the decision of the building consent authority. E3/AS1 Sections 1.0 to 3.0: values stated in the paragraphs listed