G11/AS1 Gas as an Energy Source

Where LPG cylinders can stand and how a driver reaches them, by a gas supplier's delivery guide: clearances to openings, drains and ignition sources, and the path from the truck. Then every requirement of G11/AS1, where the gas meter may go, and what the drawings show for each.

  • G11/AS1First Edition Amendment 61 Jan 2017
  • Genesis LPG guide
  • D1/AS1Second Edition Amendment 61 Jan 2017

Where the cylinders go

One LPG cylinder installation against Genesis's delivery guide: its clearances to openings, drains and ignition sources, the room around it, and the path a driver carries a cylinder along.

GroundOpenings stay out1000 mmHazardous areaCylindersOpeningIgnition sourceDrain
Drawn to one scale, with the nearest opening, drain and ignition source placed to one side of the cylinders at the distance and height given.

Genesis's conditions, not the Building Code's. Where the guide says must, a miss is marked as failing; where it says should, as a warning.

The cylinders

Around them

An openable window, a door, a vent, or any other opening into the building.

A heat pump's outdoor unit, an earthing rod, communication wiring, or anything else that can spark or burn. Give its lowest point: the hazardous area is widest at the ground.

For the driver

What this installation needs

To an opening, sideways
1000mm
Genesis p.2
Or above the valves
150mm
Genesis p.2
Hazardous area at the ground
1500mm
Genesis p.4
  1. Cylinders

    Room for 2, at least 2.

    Genesis p.1

  2. Gas stored

    90 kg in all, under 100 kg: the lighter of the guide's two drawings.

    Genesis p.2

  3. Nearest opening

    1200 mm (1.2 m) sideways from the cylinders, at least 1000 mm (1 m).

    Genesis p.2

  4. Nearest drain

    1500 mm (1.5 m) from the base of the cylinders, at least 1000 mm (1 m).

    Genesis p.2

  5. Nearest ignition source

    2000 mm (2 m) out from the nearest valve, outside the hazardous area, which reaches 1500 mm (1.5 m) out at 0 mm above the ground.

    Genesis p.4

  6. Readily ignitable material

    1500 mm (1.5 m) away, at least 1000 mm (1 m).

    Genesis p.4

  7. In front

    600 mm clear in front, at least 600 mm.

    Genesis p.1

  8. Above

    The 800 mm by 800 mm space above the cylinders is kept clear.

    Genesis p.1

  9. Path width

    900 mm wide, at least 600 mm.

    Genesis p.1

  10. From the truck

    20 m from where the truck parks, no more than 75 m.

    Genesis p.1

  11. Gradient

    5 degrees at the steepest, no more than 20.

    Genesis p.1

Reset the cylinders?

Every figure on the Cylinders page goes back to where it started. The answers on Requirements and the ticks on Show on drawings are kept.

This tool reads G11/AS1 First Edition Amendment 6, effective 1 January 2017, and Genesis's LPG Installation & Delivery Check Point Guide, Version 8, November 2019, and lists what it read, not the whole of either. G11/AS1 1.1.1 to 3.1.2 and 7.1.3: values stated in the paragraphs listed; Genesis, LPG Installation & Delivery Check Point Guide, pp.1 and 4; Genesis, LPG Installation & Delivery Check Point Guide, pp.2 and 3: dimensions as labelled on the drawings